Below is a clear, step-by-step field procedure for changing filter media in a BAC cooling tower, written the way service technicians and plant engineers actually do it.
*(This applies to BAC towers with basin strainers, side-stream filters, or cartridge/media filters—BAC itself does not use “filter media” inside the fill.)*
BAC cooling towers typically use one of these three filtration setups:
1️⃣ Cold-water basin strainer / screen
2️⃣ Side-stream filter (sand, multi-media, or cartridge type)
3️⃣ In-line Y-strainer or basket strainer
> ❗ BAC fill packs are **NOT filter media** and should never be treated as such.
✔ Lock out / tag out (LOTO) condenser water pump
✔ Stop cooling tower fan
✔ Close isolation valves to the filter
✔ Allow pressure to drop to zero
✔ Wear PPE (gloves, eye protection)
* Close inlet and outlet valves
* Open drain valve to empty the vessel
* Remove top cover / manway
* Inspect internal laterals and screens
* Vacuum out or shovel spent media
* Flush remaining fines with clean water
* Check for:
* Broken laterals
* Cracked nozzles
* Corrosion
Typical BAC-compatible multi-media arrangement:
| Layer (Bottom → Top) | Media Type |
| Support layer | Gravel |
| Intermediate | Coarse sand |
| Fine filtration | Fine sand / anthracite |
> Follow the filter manufacturer’s media depth, not BAC’s.
* Reinstall cover with new gasket
* Slowly fill filter with water
* Perform backwash until discharge runs clear
* Close valves
* Open drain and vent
* Open housing
* Pull out cartridges
* Inspect O-rings and seats
* Lubricate O-rings
* Install with correct orientation
* Torque cover evenly
* Slowly re-pressurize
* Check for leaks
* Flush to drain for several minutes
* Remove strainer basket or screen
* Wash with clean water or mild detergent
* Replace if damaged or corroded
* Reinstall securely
1️⃣ Open isolation valves
2️⃣ Start side-stream pump
3️⃣ Check pressure differential
4️⃣ Start condenser water pump
5️⃣ Start cooling tower fan
6️⃣ Verify normal basin level
| Filter Type | Typical Interval |
| Sand / multi-media | 2–5 years |
| Cartridge | 3–12 months |
| Basin strainer | Clean monthly |
*Frequency depends on water quality and blowdown control.*
❌ Treating fill as filter media
❌ Skipping backwash after media replacement
❌ Using incorrect media size
❌ Restarting pumps too quickly
❌ Ignoring broken laterals/screens
BAC strongly recommends:
* Side-stream filtration (5–10% of system flow)
* Proper chemical treatment
* Regular basin cleaning
This protects fill, spray nozzles, pumps, and heat exchangers.

Cooling Tower Fill | Cooling Tower Fan | Cooling Tower Speed Reduer | Cooling Tower Motor | Cooling Tower Drift Eliminator | Cooling Tower Fan Stacks | Cooling Tower Sprinkler Head | Cooling Tower Air Inlet Louver | Cooling Tower Basin | Cooling Tower Casing | Cooling Tower Nozzle | Cooling Tower Spray Pan | Cooling Tower Plastic Accessories
Marley/Spx | Liang Chi | Kingsun | EBABA/Shinwa | Spindle | Kuken | BAC | Brentwood | Evapco | Royden
HOME | PRODUCTS | OEM BRANDS | ABOUT US | BLOG | FAQ | CONTACT US
Cooling Tower Fill Cooling Tower Fan Cooling Tower Speed Reduer Cooling Tower Motor Cooling Tower Drift Eliminator Cooling Tower Fan Stacks Cooling Tower Sprinkler Head Cooling Tower Air Inlet Louver Cooling Tower Basin Cooling Tower Casing Cooling Tower Nozzle Cooling Tower Spray Pan Cooling Tower Plastic Accessories