Below is a clear, step-by-step field procedure for changing filter media in a BAC cooling tower, written the way service technicians and plant engineers actually do it.
*(This applies to BAC towers with basin strainers, side-stream filters, or cartridge/media filters—BAC itself does not use “filter media” inside the fill.)*
BAC cooling towers typically use one of these three filtration setups:
1️⃣ Cold-water basin strainer / screen
2️⃣ Side-stream filter (sand, multi-media, or cartridge type)
3️⃣ In-line Y-strainer or basket strainer
> ❗ BAC fill packs are **NOT filter media** and should never be treated as such.
✔ Lock out / tag out (LOTO) condenser water pump
✔ Stop cooling tower fan
✔ Close isolation valves to the filter
✔ Allow pressure to drop to zero
✔ Wear PPE (gloves, eye protection)
* Close inlet and outlet valves
* Open drain valve to empty the vessel
* Remove top cover / manway
* Inspect internal laterals and screens
* Vacuum out or shovel spent media
* Flush remaining fines with clean water
* Check for:
* Broken laterals
* Cracked nozzles
* Corrosion
Typical BAC-compatible multi-media arrangement:
| Layer (Bottom → Top) | Media Type |
| Support layer | Gravel |
| Intermediate | Coarse sand |
| Fine filtration | Fine sand / anthracite |
> Follow the filter manufacturer’s media depth, not BAC’s.
* Reinstall cover with new gasket
* Slowly fill filter with water
* Perform backwash until discharge runs clear
* Close valves
* Open drain and vent
* Open housing
* Pull out cartridges
* Inspect O-rings and seats
* Lubricate O-rings
* Install with correct orientation
* Torque cover evenly
* Slowly re-pressurize
* Check for leaks
* Flush to drain for several minutes
* Remove strainer basket or screen
* Wash with clean water or mild detergent
* Replace if damaged or corroded
* Reinstall securely
1️⃣ Open isolation valves
2️⃣ Start side-stream pump
3️⃣ Check pressure differential
4️⃣ Start condenser water pump
5️⃣ Start cooling tower fan
6️⃣ Verify normal basin level
| Filter Type | Typical Interval |
| Sand / multi-media | 2–5 years |
| Cartridge | 3–12 months |
| Basin strainer | Clean monthly |
*Frequency depends on water quality and blowdown control.*
❌ Treating fill as filter media
❌ Skipping backwash after media replacement
❌ Using incorrect media size
❌ Restarting pumps too quickly
❌ Ignoring broken laterals/screens
BAC strongly recommends:
* Side-stream filtration (5–10% of system flow)
* Proper chemical treatment
* Regular basin cleaning
This protects fill, spray nozzles, pumps, and heat exchangers.

How to Choose a Reliable China Cooling Tower FRP Fan Supplier
Top 5 Cooling Tower Fan Manufacturers And Suppliers Worldwide
Top 7 Cooling Tower Fan Manufacturers in The World: Complete Buyer Guide
Cooling Tower Fan Blade Pitch Adjustment: Steps And Best Practices
Wholesale Fill And Drift Eliminators for Marley / Evapco Cooling Tower
How To Select The Right Cooling Tower Fill Media for Replacement
Marley/Spx | Liang Chi | Kingsun | EBABA/Shinwa | Spindle | Kuken | BAC | Brentwood | Evapco | Royden
HOME | PRODUCTS | OEM BRANDS | ABOUT US | BLOG | FAQ | CONTACT US