EVAPCO cooling tower maintenance focuses on keeping thermal performance, mechanical reliability, and water quality at design levels. Below is a field-proven maintenance guide aligned with EVAPCO AT / LST / LSTE / ATWB / Counterflow & Crossflow towers.
* Check cold-water basin level
* Listen for abnormal fan or gearbox noise
* Observe fan rotation & airflow
* Check for visible drift or water leaks
* Verify make-up valve operation
* Record hot & cold water temperatures
* Inspect fan blades (cracks, pitch setting, bolt tightness)
* Check fan hub & shaft alignment
* Inspect motor mounts and vibration isolators
* Check gearbox oil level (center of sight glass)
* Inspect drive shaft couplings (if gear drive)
* Inspect and clean spray nozzles
* Check branch arms and risers for blockage
* Ensure uniform water distribution over fill
* Lubricate motor bearings (if regreasable)
* Inspect drift eliminators for plugging or damage
* Inspect fill media (scaling, biofouling)
* Check basin strainers & debris screens
* Inspect air inlet louvers
* Change gearbox oil (or per oil analysis)
* Clean cold-water basin (sludge, sediment)
* Check structural bolts & fasteners
* Inspect fan stack / fan cylinder for cracks or air leakage
* Test vibration and safety switches
* Deep clean fill and drift eliminators
* Flush spray system
* Inspect gear reducer for seal leaks and backlash
* Check fan blade pitch and rebalance if required
* Inspect corrosion on casing and structure
* Inspect and test electrical systems (motors, starters, VFDs)
* Maintain proper cycles of concentration
* Control:
* Scale
* Corrosion
* Biological growth
* Periodic Legionella risk control
* Blowdown system must operate correctly
> Poor water chemistry is the #1 cause of fill plugging and performance loss.
* Plugged spray nozzles → uneven wetting
* Low gearbox oil level → gear failure
* Incorrect fan blade pitch → overload or poor cooling
* Drift eliminator fouling → high pressure drop
* Basin sludge → pump damage
* Lockout / tagout before any work
* Never enter tower with fan rotating
* Use fall protection when working at height
* Beware of biological exposure
* Gearbox oil changes
* Fan pitch settings
* Vibration readings
* Water chemistry reports
* Parts replacement history
Cooling Tower Fill | Cooling Tower Fan | Cooling Tower Speed Reduer | Cooling Tower Motor | Cooling Tower Drift Eliminator | Cooling Tower Fan Stacks | Cooling Tower Sprinkler Head | Cooling Tower Air Inlet Louver | Cooling Tower Basin | Cooling Tower Casing | Cooling Tower Nozzle | Cooling Tower Spray Pan | Cooling Tower Plastic Accessories
Marley/Spx | Liang Chi | Kingsun | EBABA/Shinwa | Spindle | Kuken | BAC | Brentwood | Evapco | Royden
HOME | PRODUCTS | OEM BRANDS | ABOUT US | BLOG | FAQ | CONTACT US
Cooling Tower Fill Cooling Tower Fan Cooling Tower Speed Reduer Cooling Tower Motor Cooling Tower Drift Eliminator Cooling Tower Fan Stacks Cooling Tower Sprinkler Head Cooling Tower Air Inlet Louver Cooling Tower Basin Cooling Tower Casing Cooling Tower Nozzle Cooling Tower Spray Pan Cooling Tower Plastic Accessories