Views: 0 Author: Lisa Publish Time: 2025-12-27 Origin: Site
A cooling tower motor specification defines the electrical, mechanical, and environmental requirements for a motor used to drive a cooling tower fan. Below is a standard, industry-accepted specification used for BAC, Marley, EVAPCO, SPX, and similar cooling towers.
| Item | Typical Requirement |
| Motor Type | 3-phase squirrel cage induction motor |
| Rated Power | 3 HP – 300 HP (2.2 – 225 kW) |
| Voltage | 380–415 V / 460 V / 575 V |
| Frequency | 50 Hz or 60 Hz |
| Rated Speed | 720 / 900 / 960 / 1450 / 1750 rpm |
| Duty | Continuous duty (S1) |
| Service Factor | ≥ 1.15 |
| Starting Method | DOL / Star-Delta / VFD |
| Efficiency | IE2 / IE3 (NEMA Premium preferred) |
| Item | Typical Requirement |
| Mounting | Horizontal or Vertical |
| Shaft Type | Solid, stainless steel preferred |
| Bearings | Sealed / regreasable, moisture-resistant |
| Thrust Bearing | Required for vertical motors |
| Drive Type | Direct drive / Gearbox / Belt drive |
| Rotation | CW or CCW (reversible) |
| Item | Typical Requirement |
| Enclosure | TEFC or TENV |
| Protection Class | IP55 minimum (IP56 / IP66 preferred) |
| Insulation Class | Class F (Class H recommended for VFD) |
| Ambient Temp | 40 °C standard, 50 °C preferred |
| Altitude | ≤ 1000 m (derate above this) |
| Corrosion Protection | Epoxy or polyester coating |
| Humidity | 95–100% RH, non-condensing |
| Feature | Requirement |
| Outdoor Rating | Mandatory |
| Moisture Protection | Drip-proof not acceptable |
| Shaft Seal | Water-resistant |
| Paint System | C5-M or equivalent (coastal/chemical plants) |
| VFD Compatibility | Inverter-duty insulation |
| Bearing Protection | Grease relief + labyrinth seal |
> Cooling Tower Fan Motor
> 30 HP, 3-phase, 415 V, 50 Hz
> 960 rpm, TEFC, IP55
> Class F insulation, SF 1.15
> Vertical shaft with thrust bearing
> Ambient 50 °C, continuous duty
> Epoxy-coated housing, stainless steel shaft
> VFD-ready, IE3 efficiency
❌ Using standard indoor motor
❌ IP44 or drip-proof enclosure
❌ No thrust bearing for vertical motor
❌ Service factor = 1.0
❌ No corrosion protection
Wholesale Fill And Drift Eliminators for Marley / Evapco Cooling Tower
Cooling Tower Speed Reducer Supplier | Industrial Gear Reducers
Top 10 Cooling Tower Fill Replacement Suppliers in Argentina
Top 10 Cooling Tower Fill Replacement Suppliers in Bangladesh
Top 10 Cooling Tower Fill Replacement Suppliers in East Timor
Marley/Spx | Liang Chi | Kingsun | EBABA/Shinwa | Spindle | Kuken | BAC | Brentwood | Evapco | Royden
HOME | PRODUCTS | OEM BRANDS | ABOUT US | BLOG | FAQ | CONTACT US