Here’s a detailed EVAPCO Cooling Tower Maintenance Checklist — suitable for closed-circuit and open-circuit towers. Regular maintenance helps ensure efficient operation, energy savings, and extended equipment life.
| Task | Description |
| Visual Inspection | Check for unusual noise, vibration, or leaks |
| Water Level | Ensure basin water level is within operating range. Adjust make-up valve if necessary |
| Pump Operation | Verify pump operation and check for leaks or noise |
| Fan Operation | Observe fan rotation, noise, and balance. Check VFD operation (if applicable) |
| Strainers | Inspect and clean strainers to prevent clogging |
| Bleed-off | Confirm bleed-off system is functioning to control water chemistry |
| Task | Description |
| Water Treatment | Test and adjust water chemistry (pH, conductivity, hardness, biocide) |
| Fill Media / Coil Surfaces | Inspect for scale, slime, algae, or debris. Clean if fouling is visible |
| Fan Motor | Check for overheating, vibration, or noise. Inspect electrical connections |
| Belts (if belt-driven) | Inspect tension, alignment, and wear. Adjust or replace if needed |
| Nozzles / Spray System | Inspect for clogging; clean or replace as required |
| Drift Eliminators | Inspect for damage or clogging. Clean if necessary |
| Task | Description |
| Basin Cleaning | Drain and remove sediment, sludge, or biological growth |
| Coil Cleaning (Closed Circuit) | Clean coil surface with water or chemical coil cleaner to maintain heat transfer |
| Fan Blades | Check for cracks, corrosion, and tightness. Clean blades. |
| Vibration Check | Measure and record fan vibration levels. Investigate abnormal readings |
| Electrical Components | Inspect starter, contactors, wiring, and control panel. Tighten connections. |
| Task | Description |
| Motor Bearings | Lubricate per manufacturer’s recommendation (if applicable) |
| Fan Shaft Bearings | Inspect and lubricate bearings. Replace if worn |
Gear Drive / Belt Drive | Check oil level and change if dirty; inspect alignment. |
| Structural Components | Inspect casing, supports, access doors, ladders for corrosion or damage. Touch up coating. |
| Task | Description |
| Full System Inspection | Comprehensive check of mechanical, electrical, and water systems |
| Deep Cleaning | Descale fill, clean coil with approved chemicals, disinfect basin and piping |
| Winterization (if seasonal) | Drain system or add glycol solution. Protect against freezing |
| Component Replacement | Replace worn-out belts, seals, gaskets, and filters. |
| Calibration | Calibrate sensors (temperature, conductivity, level) |
| Parameter | Recommended Range |
| pH | 6.5 – 9.0 |
| Conductivity | As per local water treatment guidelines |
| Calcium Hardness | 50–500 ppm |
| Total Alkalinity | 50–500 ppm |
| Chlorides | < 250 ppm |
| Silica | < 150 ppm |
Lock out/tag out (LOTO) before performing maintenance.
Use PPE (gloves, goggles, mask) during chemical handling and cleaning.
Follow EVAPCO’s official Operation & Maintenance Manual for your model.
Cooling Tower Fill | Cooling Tower Fan | Cooling Tower Speed Reduer | Cooling Tower Motor | Cooling Tower Drift Eliminator | Cooling Tower Fan Stacks | Cooling Tower Sprinkler Head | Cooling Tower Air Inlet Louver | Cooling Tower Basin | Cooling Tower Casing | Cooling Tower Nozzle | Cooling Tower Spray Pan | Cooling Tower Plastic Accessories
Marley/Spx | Liang Chi | Kingsun | EBABA/Shinwa | Spindle | Kuken | BAC | Brentwood | Evapco | Royden
HOME | PRODUCTS | OEM BRANDS | ABOUT US | BLOG | FAQ | CONTACT US
Cooling Tower Fill Cooling Tower Fan Cooling Tower Speed Reduer Cooling Tower Motor Cooling Tower Drift Eliminator Cooling Tower Fan Stacks Cooling Tower Sprinkler Head Cooling Tower Air Inlet Louver Cooling Tower Basin Cooling Tower Casing Cooling Tower Nozzle Cooling Tower Spray Pan Cooling Tower Plastic Accessories