In the cooling tower system, the circulating water pump (also known as the cooling tower pump or circulating pump) is the core equipment that ensures efficient dissipation of heat load. Proper selection of circulating water pumps can not only ensure stable operation of the cooling tower system, but also significantly reduce energy consumption and maintenance costs. This article will comprehensively introduce how to correctly select cooling tower circulating water pumps from principles, key parameters, calculation steps to selection considerations.
![]() | ![]() |
The main function of the cooling tower circulating water pump is to transport the high-temperature water that absorbs heat from equipment (such as air conditioning units, condensers, process heat exchangers, etc.) to the cooling tower, and then return it to the equipment after heat dissipation, thus forming a stable closed-loop cooling circuit.
A well-designed water pump selection should meet the following requirements:
Flow rate is the most critical parameter for selecting cooling tower pumps, which can generally be determined through the following methods:
Common experience points:
Industrial cooling tower: 1 RT ≈ 0.27-0.32 m ³/h
Central air conditioning cooling tower: 1 RT ≈ 0.3 m ³/h (commonly used)
For example, a 500RT cooling tower
Flow rate=500 × 0.3=150 m ³/h
If the equipment manufacturer provides a rated flow rate, the equipment flow rate should be used as the standard.
The head of the water pump needs to overcome the following resistance:
1. System static pressure difference (if there is a high-level cooling tower, the building height should be considered)
2. Friction loss in pipelines (straight pipes, elbows, tees, valves, etc.)
3. Spray resistance of cooling tower (generally 3-8m)
4. Condenser resistance (usually 30-60kPa ≈ 3-6m, but data needs to be checked)
5. Safety margin (10% -20%)
The higher the efficiency of the water pump, the lower the operating cost.
When selecting, the appropriate model and motor power are usually determined based on the manufacturer's sample.
1.Cooling tower: 600RT
2.Total length of pipeline: 80 meters
3.Piping: DN150
4.Cooling tower resistance: 5 meters
5.Condenser resistance: 45 kPa (≈ 4.5 m)
6.Height difference: 5 meters
7.Friction loss of pipeline: 12 meters
8.Safety margin: 10%
Flow rate=Cold ton × 0.3
= 600 × 0.3
= 180 m³/h
Total head=height difference+pipeline friction loss+cooling tower resistance+condenser resistance
= 5 + 12 + 5 + 4.5
= 26.5 m
Add a 10% safety margin:26.5 × 1.1=approximately 29 meters
Therefore, the selected lift should not be less than:
29 meters (taking 30 meters)
Based on the manufacturer's curve, select:
1.Flow rate: 180 m ³/h
2.Lift: 30 meters
3.Power: Approximately 15-22 kW (slightly different manufacturers)
High water temperature (32-37 ° C) can easily cause cavitation, and sufficient NPSHa should be left.
Avoid "air blockage" affecting the flow rate.
For example, the resistance of counter current tower and cross current tower is different.
If the system may increase its cooling capacity in the future, a slightly higher flow rate should be selected.
It is recommended to use dual or triple pumps in parallel to improve regulation efficiency.
Supply Cooling Tower Filler From Manufacturer To Global Buyers
Jual Filler Cooling Tower in Indonesia: A Complete Buyer's Guide
How To Choose The Right Cooling Tower Infill for Your System
Cooling Tower Filling Replacement: When And How To Replace It
Cooling Tower Fill Media for HVAC And Industrial Cooling Systems
BAC Cooling Tower Fill Replacement: A Complete Buyer’s Guide
Fills in Cooling Tower: Types, Materials, Functions, And Benefits
Cooling Tower Infill Replacement Suppliers: How To Choose The Best
Finding the Right Cooling Tower Fill Supplier for Your Project
Marley/Spx | Liang Chi | Kingsun | EBABA/Shinwa | Spindle | Kuken | BAC | Brentwood | Evapco | Royden
HOME | PRODUCTS | OEM BRANDS | ABOUT US | BLOG | FAQ | CONTACT US